Short communication
Partial discharge study in transformer oil due to particle movement under DC voltage using the UHF technique

https://doi.org/10.1016/j.epsr.2008.03.022Get rights and content

Abstract

Converter transformers are one of the key components in high voltage DC power networks. The insulation of these transformers is stressed by both AC and DC voltages. Therefore, AC and DC voltage tests are routinely applied during factory tests to verify the performance of the insulation structure. Partial discharges in an insulation system are incipient discharges that can damage materials and may eventually lead to complete failure of the insulation system during operation. Recently it has been shown that monitoring such discharges formed under AC stress is feasible using Ultra High Frequency (UHF) measurement technique and that there is a reasonable correlation between the partial discharge magnitude and the amplitude of the UHF signal generated by partial discharges. However, the partial discharge activity under DC voltages is not fully understood. This paper describes a study using the UHF technique to improve our understanding of particle-induced partial discharge activity under DC voltages in mineral oil insulation. UHF signals generated due to conducting particle contamination in transformer oil under AC and DC voltages are compared and analyzed. A method for distinguishing particle discharges in regions of high or low electric field stress is proposed based on frequency-domain analysis of the measured UHF signal.

Introduction

High voltage DC power transmission networks are becoming more widespread and converter transformers are key components of these systems. Mineral insulating oil plays a major role in power transformers, acting both as insulant and coolant. The increasing use of large converter transformers means that it is important to ensure that the insulation systems for this type of plant are reliable.

The performance characteristics of converter transformer insulation are verified by carrying out routine tests in the factory, including AC voltage withstand test, DC voltage test, polarity reversal test, etc. [1], [2]. The DC voltage test is severe compared to AC voltage test because movement of conducting particles towards HV conductors can be sustained in a single direction in contrast with their more erratic motion in an AC field. Under certain conditions, DC voltages could initiate the process of degradation and lead to earlier failure of a transformer. At present, the routine DC tests have limitation to measure the incipient discharges, if the electrical noise in the ambience is high. It is also recommended in standard to use ultrasonic technique to classify the partial discharges from the noise [1]. Adoption of UHF technique for identification of partial discharges under DC voltage test in transformer is at infancy stage. Therefore, a potential diagnostic opportunity is being missed.

The presence of even a minor defect in the insulation structure, under normal operating voltages can create local field enhancement causing partial discharges such as corona/surface discharges. The defect may be a due to protrusion from the winding or due to floating conducting/non-conducting particles present in the transformer oil. The non-conducting defect would typically be fibre dust from the press-board or paper insulation surfaces. Conducting defects may be particles in the transformer oil introduced during manufacture/maintenance or from wear and tear of metal parts within the oil cooling system during operation. If the level of contamination is high, under the DC test contaminated particles may align in the direction of electrical field helping to bridge part of the windings or instigate a short circuit from an HV component to earth. Krins et al. [3] observed that a conducting particle affects the breakdown strength of the oil more than the insulating particle. Some literature is available dealing with particle initiated breakdown in transformer oil under AC and DC voltages [4], [5] but further research is essential to understand the polarity of the applied voltage on partial discharge formation due to particle movement.

Birlasekaran has studied particle movement in transformer oil under AC and DC fields both theoretically and by experimental study [6], [7]. He concludes that under DC voltages, conductive particles transport charge by contact with electrodes and observed the discharge current in the form of a fast rising current pulse and slowly increasing displacement current [7]. Dascalescu et al. [8], studied particle movement in insulating fluids and concluded that the vertical amplitude of particle bounces increases with electric field up to the point at which micro-discharges occur between the particle and the electrode of opposite polarity.

In addition to the conventional IEC60270 [9] measurements, methods for identification of partial discharges include optical techniques (characterising the light emanating from discharges), detecting acoustic emissions, chemical methods (such as fluorescence measurement, dissolved gas analysis or high performance liquid chromatography) and by radio frequency measurement [10], [11], [12], [13].

When PD current pulses involves rise and fall times of a nanosecond or less, signals in the Ultra High Frequency (UHF) range (300–3000 MHz) are excited [13], [14]. The UHF technique for partial discharge identification in transformers is gaining acceptance due to its high sensitivity and good signal to noise ratio [13]. Considerable research activity has been carried out on PD activity in transformer oil insulation, e.g., [15], [16]. Measurements have indicated that the UHF signals radiated by partial discharges propagate at the speed of light in oil gets attenuated by a factor of square root of dielectric constant of the liquid (∼2 × 108 m s−1) and are attenuated by about 6 db per 10 m of travel [17]. Judd et al. [18], [19] has provided an extensive review on partial discharge monitoring in transformers using the UHF technique, where details of the sensors, signal interpretation and the applicability of the technique in a practical situation can be found. Jongen et al. [20] carried out studies on partial discharge activity in transformer oil under AC voltages and concluded that phase-resolved UHF signals can help to classify the type of PD source. Meijer et al. studied partial discharge activity in transformers using UHF technique and concluded that noise free phase-resolved partial discharge patterns could be obtained using the narrow band UHF technique [21].

The UHF PD detection technique is effectively a tool for Non-Destructive Testing (NDT) and can identify active defects present in the insulation structure during operation. However, its application to transformers in the field as a condition monitoring system is still limited. Further research is needed to lay the foundations for understanding the characteristics of UHF signals generated due to incipient discharges formed under DC voltages to improve confidence for its use by engineers carrying out DC tests on converter transformers. Hence an attempt has been made in the present study to understand the feasibility of applying UHF sensors for identification of partial discharge activity in transformer oil under DC voltages.

Section snippets

Experimental

The experimental setup used for the present study is shown in Fig. 1. AC voltages were generated using a test transformer rated at 50 Hz, 1.25 kVA, 0–50 kV. DC voltages were produced using a 0–100 kV, 1 mA supply source. Both applied AC and DC voltages were measured using a high voltage probe (Tektronix model. No. P6015A) connected to digital oscilloscope.

The test cell used in the present work is shown in Fig. 2. It consists of two electrodes in a cylindrical container filled with transformer oil

Results and discussion

When energised, the particle in the test cell was observed to levitate at 9 kV under DC voltages and at 15 kVrms under AC voltages. These levitation voltages were established based on the first pulse being captured by the oscilloscope from the UHF sensor output. Inception always occurred at lower voltages under DC compared to AC voltage.

The presence of a conducting particle in the oil gap in contact with one of the electrodes enhances non-uniformity of the electric field in the gap in a way

Conclusions

It is realized that the UHF signals are generated due to partial discharges caused by the motion of conducting particles transformer oil under DC voltages. The magnitude of UHF signals is higher under DC voltage compared to that under AC voltage, confirming that it is possible to identify any incipient discharge that occurs during the AC/DC voltage routine test of electrical plant, allowing one to take any remedial action.

It is confirmed based on the present study that the PD inception voltage

Acknowledgements

This research is published as part of the EPSRC Supergen V. Consortium, Asset Management and Performance of Energy Systems (AMPerES). The authors wish to thank Mr. J. Barrasford for his help in arranging the experimental setup.

References (25)

  • Subbiah Deepa et al.

    Synchronous fluorescence and excitation emission characteristics of transformer oil ageing

    Talanta

    (2006)
  • IEEE Trial use standard general requirements and test code for oil immersed HVDC converter transformers, IEEE Std...
  • W. Kennedy

    Recommended dielectric tests and test procedures for converter transformers and smoothing reactors

    IEEE Trans. Power Deliv.

    (1986)
  • M. Krins et al.

    Influence of carbon particle on the breakdown voltage of transformer oil

  • F. Carraz et al.

    Particle initiated breakdown in quasi uniform field in transformer oil

    IEEE Trans. Dielectr. Electr. Insul.

    (1995)
  • P. Rain et al.

    Behaviour of free conducting particle and their role on breakdown in oils under AC and DC voltage

  • S. Birlasekaran

    The movement of a conductive particle in transformer oil in AC fields

    IEEE Trans. Electr. Insul.

    (1993)
  • S. Birlasekaran

    The measurement of charge on single particles in transformer oil

    IEEE Trans. Electr. Insul.

    (1991)
  • Lucian Dascalescu et al.

    Modeling of conductive particle behavior in insulating fluids affected by DC electric fields

    IEEE Trans. Ind. Appl.

    (1998)
  • IEC 60270

    High Voltage Test Techniques-Partial Discharge Measurement

    (December 2000)
  • M. Duval

    A review of fault detectable by gas in oil analysis in transformers

    IEEE Electr. Insul. Mag.

    (2002)
  • P.M. Eleftherion

    Partial discharge XXI: acoustic emission based PD source location in transformers

    IEEE Electr. Insul. Mag.

    (1996)
  • Cited by (54)

    • Motion characteristics and distribution of metal particles in insulating oil under DC voltage

      2023, Experimental Thermal and Fluid Science
      Citation Excerpt :

      The common solid impurity phases include the metal particles, fibers and paper scraps [3–4]. During transformer operation, the flowing contaminated oil forms an impurity-containing oil flow with two-phase flow characteristics [5]. Moreover, the physical properties and the force applied on impurity particles directly determine their motion and distribution in the oil, and then consequently affect the insulation characteristics of transformer oil from the aspects of electric field distortion and interface interaction [6–8].

    • Impact of impulse voltage frequency on the partial discharge characteristic of electric vehicles motor insulation

      2020, Engineering Failure Analysis
      Citation Excerpt :

      Nevertheless, even with the state-of-the-art PD systems, it is extremely difficult to detect PD for impulse voltage waveforms with good S/N ratio at high frequencies while simultaneously obtaining stable repetitive PDIV under the influence of noise generated by the switching power electronics devices. When PD current pulses involves rise and fall times of a nanosecond or less, signals then the Ultra High Frequency (UHF) range 300–3000 MHz is approved sensor due to its high sensitivity and good signal to noise ratio [12–16]. The PD test setup schematic diagram demonstrated in Fig. 1 containing an impulsive voltage generator, an ultrahigh-frequency (UHF) antenna, high frequency oscilloscope, testing specimen, a high voltage probe, data collecting control system and PC.

    • Statistics based method for partial discharge identification in oil paper insulation systems

      2018, Electric Power Systems Research
      Citation Excerpt :

      Various PD detection and analysis methods based on different physical phenomena accompanied by a PD generation have been presently known and applied for electrical power apparatus diagnostics [8,25–28]. The most commonly applied are inter alia: acoustic emission (AE) method based on a sound wave generation during a PD activity [15,29–32], spectrophotometry method based on a light emission [7,9,33], thermovision method, based on a heat emission [34], dissolved gas analysis (DGA) method [12,35,36], based on chemical reactions results, electrical method (EM), so-called a conventional method, based on a current pulse analysis [37–42], transient earth voltage (TEV) [39], based on an electromagnetic radiation in high frequency range, and ultra-high frequency (UHF) method [43–47], based on a radio frequency radiation. From among all of those techniques only an electrical method is a direct PD measurement method, which means it delivers exact information about testing phenomena, i.e. an apparent charge value.

    View all citing articles on Scopus
    1

    He is currently with the University of Strathclyde, Glasgow, as an Academic Visitor.

    View full text